104-IIRO-16

 
acces i/o logo
  US Pricelist
CND Pricelist
Privacy and Security Policy



Isolated Digital Input and Relay Output Card

Features

  • 16 optically-isolated, non-polarized CMOS compatible digital inputs accept ±31VDC or AC rms
  • IRQ on input change of state (COS) eliminates the need for constant polling
  • Slow/fast filter to accommodate AC voltages and noisy DC inputs
  • 16 long-life form C electro-mechanical relays switch up to 1A each
  • Factory Options: (call for pricing and availability)
    • Economy version without COS feature
    • Input only and relay only versions
    • Expanded input voltage levels
    • RoHS Available. Please contact us for ordering information


The 104-IIRO-16 is a low-cost board that provides isolated input and output for PC/104 Bus computer applications. The board has sixteen optically-isolated digital inputs for AC or DC control signals and sixteen electro-mechanical relay outputs. The Change of State Detection capability of ACCES' Model 104-IIRO-16 sets this board apart from the competition. An Economy version can be ordered as Model 104-IIRO-16E which has no Change of State Detection or IRQs. Also available is Model 104-RO-16 which has 16 relay outputs only.

 

INPUTS

The isolated inputs can be driven by either AC or DC and are not polarity sensitive. Input signals are rectified by opto-coupler diodes. A 1.8KΩ, ½ Watt resistor in series provides current limiting. The input voltage range is 3V to 28V (rms). To extend the input voltage range, you may connect external resistors in series with the input.

Each input circuit is switch selectable for slow/fast filter that has a 4.7 millisecond time constant. The filter must be selected for AC inputs in order to eliminate response to AC noise. The filter is also valuable for use with slow DC input signals in a noisy environment. The filter may be switched out for DC inputs in order to obtain faster response. Filters are manually switched individually on or off.

INTERRUPTS

Interrupts are enabled/disabled by software. When the change-of-state detection circuit is enabled, the card asserts an interrupt whenever any of the sixteen isolated inputs change state. Once an interrupt has been generated and serviced, it is automatically cleared. This feature greatly frees up system resources by eliminating the need for constant polling to see when an input has changed state.

OUTPUTS

The electro-mechanical relay outputs are comprised of two groups of eight form C SPDT outputs.

CONNECTIONS

The relay outputs are accessed via a 50 pin header type connector, while the isolated inputs are accessed via a 34 pin type header connector.

UTILILTY SOFTWARE

104-IIRO-16 utility software provided on CD includes sample programs in a variety of languages for DOS / Windows 95/98/NT4/2000/XP and 2003. A Windows graphical setup program is also provided, and a "C" language sample for Linux.

Specifications


Isolated Digital Inputs

  • Number of Inputs: Sixteen
  • Type: Non-polarized, optically-isolated from each other and from the computer. (CMOS compatible).
  • Voltage Range: 3 to 31V DC or AC RMS (50 to 10 KHz)
  • Isolation: 500V
  • Input Resistance: 1.8KΩ in series with opto-coupler.
  • Response Time: 4.7 milliseconds w/filter, 10usec w/o filter

Relay Outputs

  • Number of Outputs: Sixteen
  • Type: SPDT Form C Relay - OMRON G5V-1
  • Contact Ratings: 1A @ 24VDC (60VDC max), 0.5A @ 125VAC carry current
  • Contact Type: Ag with Au clad (bifurcated contacts optional)
  • Contact Arrangements: Channels 0-15: SPDT Form C.
  • Contact Resistance: Initial, 100 mΩ maximum.
  • Contact Life: Mechanical: 5 million operations minimum.
  • Operating Time: 5 milliseconds maximum.
  • Release Time: 5 millisecond maximum.
  • Regulatory Approvals: UL and CSA.

Interrupts

  • When enabled by software, interrupts are generated when any digital input changes state (High to Low or Low to High, and from signal to no signal with AC inputs).

Power Required

  • 5VDC at 0.5A (all relays ON).

Environmental

  • Ambient Temperature: Operating: -30°C to 70°C. (non-icing)
  • Weight: Approx. 4.5 oz. (~130 grams).

CE testing & approval must be done at the system level, in the designed enclosure, and is not done on individual boards.

When ordering RoHS products, please identify this need by using a unique model number suffix, "-RoHS" on all orders. For pricing and lead times, please contact your sales representative.
Part NumberPrice(USD)
104-IIRO-16
104-IIRO-16E
104-RO-16
View / Download Data Sheet (in .pdf format)


View / Download Manual (in .pdf format)
Acquisition Control Communications Engineering / Systems
 
 
 
USA Office

Tel:1.877.902.2979-1.425.223.4311
Fax:1.877.329.4324
Address: 1480 Gulf Road, Suite 837,
PO Box 1364
Point Roberts, WA 98281

Western Canada - Vancouver BC

Tel:1.800.663.6001 or 1.604.925.6150
Fax:1.604.925.6170
Address: 2454 Haywood Ave
West Vancouver, BC V7V 1Y1

Eastern Canada - Markham, Ontario

Tel:1.800.465.0164 or 1.905.513.7027
Fax:1.877.329.4324